Dissolved Gas Analysis Plays Key Role in Transformer Operations
Purity of gases is critical to preventing atmospheric contamination
and resultant power failures
So much attention is paid to what comes out of the stack
and for good reason, pollutants such as SO2 and NO are detrimental
to the environment. However, as the electricity is delivered
to the power grid, transformers play an important role in
converting high voltage to domestic use. It is in these mineral
oil-filled transformers that constant monitoring and maintenance
is critical in preventing ill-timed failures. Blackouts give
power companies black eyes and reduced profits.
The dissolved
gas analysis (DGA) technique is an important tool for monitoring
and troubleshooting a transformer’s operational condition. There are
four basic transformer fault types categorized by severity.1 Arching, the most
severe transformer fault, produces significant amounts of hydrogen and acetylene
as the mineral oil breaks down. If cellulose insulating paper is exposed to
the arching, then carbon dioxide (CO2) and carbon monoxide (CO) will be present.
Next
in severity is localized heating or sparking due to intermittent high voltage
flash without current. The symptomatic gases produced are increased
levels of methane and ethane. Third in severity is localized overheating.
Overheating as an example may be caused by electrical contact
failure, which produces ethylene
and methane gases. If severe overheating occurs, then trace amounts of acetylene
may be present.
Lowest is severity is a low-energy electrical discharge
that is sometimes referred to as a corona event. This low-order
fault will produce hydrogen
and methane
with traces of ethane and ethylene. If the low-energy discharge occurs
within
the cellulose insulation paper, then CO2 and CO will be present.2
Periodically,
transformer oil samples are collected as a key part of
a preventative maintenance program. The sample is then subject
to high vacuum,
degassed
and analyzed by gas chromatography. The following discussion of support
gas systems
highlights the gas chromatograph (GC) use of the thermal conductivity
detector
(TCD) and the flame ionization detector (FID) in DGA. Figure 13 illustrates
the basic components of a GC system. The system includes a carrier gas
source, flow controller, sample injection port, column, column oven,
detector and
data reporting system. The collected sample is introduced into the system
and swept
by the carrier gas into the column for separation. The column at elevated
temperatures elutes or exhausts compounds at distinctive intervals for
analysis by the detector.
It is not uncommon for the GC to have a TCD
preceding a FID for detection of molecules without the
carbon-hydrogen bond. For instance, when a fault
occurs
near the cellulose insulation, nitrogen (N2), oxygen (O2), CO2 and
CO may be produced. The TCD compares the thermal conductivity
of the carrier
gas
to the
sample-carrier gas mixture. The design utilizes separate reference
and sample cells, which use metal filaments or thermistors
to sense temperature
change.
An electrical resistance is established, producing a signal proportional
to the concentration of the sample in question.5 Helium is the desired
carrier gas because hydrogen may be the fault gas of interest.

Figure 1. Basic gas chromatograph components The FID is an extremely sensitive method for detecting hydrocarbon
fault gases like methane, ethane, ethylene and acetylene.
These gases are key indicators of arcing, corona or sparking
type transformer faults. Differing slightly from the TCD,
the sample elutes from the column and is mixed with hydrogen
and a make-up gas before entering the FID flame nozzle
head as illustrated in Figure 2.3 The mixture is combined
with air and burned while being exposed to a voltage bias
between the nozzle and collector plate or electrode. The
sample gets converted to ions. A current is establishes
and converted to a voltage signal proportional to the samples
mass as a function of time.4 The exhaust gases are then
vented out the top of the detector.

Figure 2. FID nozzle schematic
In either detector gas purity plays an important role in
column performance and stability. Chromatogram peak trailing,
ghost peaks or drifting base lines are symptoms that column
contamination or damage has occurred. It is imperative to
minimize atmospheric contamination. Polymer tubing should
not be used for the carrier gas because it permeates oxygen
and moisture over time. The partial pressure differential
provides the driving force for the impurity to permeate the
polymer tubing wall. Ideally, stainless tubing should be
used in all gas connections because copper will permeate
moisture. A dual-stage cylinder regulator as illustrated
in Figure 3 should be constructed from barstock raw material
to minimize the whetted surface area. The internal geometry
can be machined to eliminate dead ends and other entrapment
sites to enhance purging. It is critical that the diaphragm
material be 316L stainless versus neoprene to eliminate atmospheric
permeation and plasticizer off gassing.

Figure 3. (GC) Dual-Stage
regulator
Another key feature of a gas chromatograph (GC) regulator is the integral gas
bottle gland check valve. The location of the check valve prevents atmosphere
from being exposed to the gas system during a cylinder exchange. As an additional
precaution the (GC) regulator should have an interstage purge. This feature
will minimize the exposure of the .0225 cm3 of trapped atmosphere between
the cylinder and the internal check valve. The GC regulator utilizes the
high load marginal spring of the second-stage seat for isolation. The interstage
diaphragm valve can then be used to flush or displace the contaminants. The
first stage preset pressure of 225 psi enables the technician to perform
a pressure-time cycle purge. This will reduce the contaminant level below
the 1 ppm level.
The DGA is a critical element of any oil transformer maintenance
program. With proper care of the GC gas delivery system, flame ionization
and thermal conductivity
detectors can provide the resolution to monitor the type and concentration
of fault gases. This will provide insight of impending transformer problems
so the power company can schedule preventative maintenance. Ultimately, the
black eye can be avoided while meeting the public’s insatiable demand
for electricity.
References:
- Northern Technology & Testing, Fault Types, http://www.nttworldwide.com/faults.htm
- USA Industrial Group, Transformer Oil Testing, http://www.usaindustrialgroup.com/transoiltest6.htm
- Sheffield Hallam University, Biosciences http://teaching.shu.ac.uk/hwb/chemistry/tutorials/chrom/gaschrm.htm
- Hinshaw, J, “The Flame Ionization Detector” LCGC
North America, Dec. 2005. http://chromatographyonline.findpharma.com/lcgc/GC/The-Flame-Ionization-Detector/
- Hinshaw, J, “The Thermal Conductivity Detector” LCGC
North America, Jan. 2006. http://chromatographyonline.findpharma.com/lcgc/GC/
NOTE: This article appeared in the June 2008 issue of Pollution
Engineering)
Richard Green is Manager of Business Development, CONCOA,
manufacturers of gas flow control systems and equipment,
headquartered in Virginia Beach, VA, 800-225-0473, richard.green@concoa.com,
www.concoa.com.
|